Evaluation of heat exchange performance for intermediate heat exchanger in HTTR

Tochio, Daisuke; Nakagawa, Shigeaki

JAERI-Tech 2005-040, 39 Pages, 2005/07

JAERI-Tech-2005-040.pdf:1.88MB

In High Temperature Engineering Test Reactor (HTTR) of 30 MW, the generated heat at reactor core is finally dissipated at the air-cooler by way of the heat exchangers of the primary pressurized water cooler and the intermediate heat exchanger. Heat exchangers in main cooling system of HTTR should satisfy two conditions, achievement of reactor coolant outlet temperature 850 $$^{circ}$$C/950 $$^{circ}$$C and removal of reactor generated heat 30 MW. That is, heat exchange performance should be ensured as that in heat exchanger designing. In this report, heat exchange performance for Intermediate heat exchanger (IHX) in main cooling system is evaluated with rise-to-power-up test and in-service operation data. Moreover, the applicability of IHX thermal-hydraulic design method is discussed with comparison of evaluated data with designed value.

JAEA Reports

Change in heat exchange performance of VCS cooler and its recovery works

Hamamoto, Shimpei; Watanabe, Shuji; Oyama, Sunao*; Ota, Yukimaru; Tochio, Daisuke; Fujimoto, Nozomu

JAERI-Tech 2005-035, 35 Pages, 2005/07

JAERI-Tech-2005-035.pdf:2.54MB

The Vessel Cooling System (VCS) is one of the safety engineered features of the HTTR. The VCS removes the decay heat of the reactor core when the forced circulation can not be maintained due to pipe rupture accidents, etc. VCS cools the core by water cooling panels surrounding the reactor pressure vessel. The VCS also keeps the temperature of the concrete of the primary shielding under the design limit during the operation. The temperature of cooling water of the VCS has recently tended to rise gradually, though the amount of heat removal of VCS has been constant. Accompanying with the increase of the cooling water temperature, the temperature of the shielding concrete is also possible to rise and exceed the limit. The heat exchange performance of the VCS cooler was evaluated and the deterioration of the cooler was verified. Therefore, the cleaning of heat transfer tubes was carried out to recover the heat exchange performance. The cleaning recovered the performance of the VCS cooler drastically and the cooling water temperature of the VCS could be reduced sufficiently.

Journal Articles

Heat exchanger performance in main cooling system on high temperature test operation at High Temperature Gas-Cooled Reactor 'HTTR'

Tochio, Daisuke; Nakagawa, Shigeaki; Furusawa, Takayuki*

Nihon Genshiryoku Gakkai Wabun Rombunshi, 4(2), p.147 - 155, 2005/06

High Temperature Engineering Test Reactor (HTTR) of high temperature gas-cooled reactor at JAERI achieved the reactor outlet coolant temperature of 950$$^{circ}$$C for the first time in the world at Apr. 19, 2004. To remove of generated heat at reactor core and to hold reactor inlet coolant temperature as specified temperature, heat exchangers in HTTR main cooling system should have designed heat exchange performance. In this report, heat exchanger performance is evaluated based on measurement data in high temperature test operation. And it is confirmed the adequacy of heat exchanger designing method by comparison of evaluated value with designed value.

JAEA Reports

Status and Future Studies of the IHX Design of the ex.VHTR

; ; *; *; *; *; *; *

JAERI-M 85-182, 304 Pages, 1985/11

JAERI-M-85-182.pdf:9.26MB

no abstracts in English